Split systems have separate indoor and outdoor units, making it easier to integrate a reversing valve. This valve enables the system to reverse refrigerant flow, allowing the heat pump to operate for defrosting in winter or cooling in summer.
Many split systems share components (e.g., compressors and coils) with heat pumps made by the same brand, simplifying the conversion process. During conversion, the cooling function is often disabled, and the indoor wall unit is replaced with a condenser.
Efficiency and Compressor Type
Converted air conditioners typically have lower efficiency (COP) compared to dedicated heat pumps. Air conditioners are optimized for cooling, where the compressor operates efficiently within a limited pressure and temperature range.
In heating mode, the outdoor coil must collect low-potential heat from ambient air, a task for which it is not optimized.
Systems with rotary compressors achieve a lower heating factor than those with scroll compressors; inverter compressors improve efficiency by modulating output.
Refrigerant Compatibility
Air conditioner refrigerants are not optimized for heat absorption at low temperatures, which can limit performance. Switching refrigerants often requires significant system modifications.
Essential Components for Heat Pump Operation
Operating Unit (Controller): Automates defrost cycles, regulates system performance, manages compressor operation, and ensures safety with connected flow, temperature, and pressure sensors.
Accumulator: Protects the compressor by ensuring only vapor enters. This prevents damage from liquid refrigerant returning from the outdoor coil during heating.
Check Valves: Necessary if thermostatic expansion valves (TXVs) are used to ensure proper refrigerant flow direction in both heating and cooling modes
Safety Switches: If the air conditioner lacks high-pressure and low-pressure safety switches, these must be added or adjusted to prevent system damage.
A) Bi-Directional Metering Device or B) thermostatic expansion valves (TXVs) with check valves allow proper refrigerant flow regulation in both directions. Standard air conditioners lack this feature and require upgrades during conversion.
Condenser for heat pump
The condenser is the heat pump exchanger on its secondary circuit. The hot
refrigerant in the condenser transfers heat to the heating water. The hot
refrigerant enters the exchanger in the vapor phase and is cooled, condensed
and subcooled after condensation. The heat transferred to the heating water
comes mainly from the change of state (i.e. condensation of the refrigerant).
The list shows plate heat exchangers often used as condensers:
SWEP B8LASH (for capacities of 3–10 kW, B8LASH is asymmetric; connections are combo ¾"),
SWEP B26H,
B26FH (asymmetric exchanger 5–20 kW designed for heat pumps; it has soldering connections towards the primary, external thread ISO G 1" towards the secondary circuit),
SWEP B18H, B185H, B16DW (for natural gas, CO2 up to 140 bar; connections according to customer's request),
The asymmetric exchanger has narrower channels in the internal circuit (designed for
refrigerant). There is usually about 10 times more flow on the
water side than on the refrigerant side. So asymmetric heat exchanger is
optimized for air conditioning and heat pumps.
The SWEP B25TH version is popular among technicians because it has pure solder
connections on the refrigerant side. SWEP B85H and B86H have a higher efficiency
compared to B25TH, their connections are combo: the
connections are externally threaded and also provide inner pipe for soldering
(see picture, click to open the connection's drawing). B86H achieves the
highest efficiency, but it also has the highest pressure losses. Pressure
losses can be reduced by increasing the number of plates.
All SWEP heat exchangers have stainless steel connections
and a silver solder containing at least 45 % silver has to be
used.
Heat exchangers for heat pumps
Overview of condensers for heat pumps, i.e. the exchanger serves as
a refrigerant condenser. The pressure losses for the water circuit (heating)
are shown within the table. The condenser calculation is for the R410A refrigerant on the
primary side, the water on the secondary side has gradient of
.
The design pressure of the exchanger can be obtained from the graph provided
in its product sheet. The design pressures of common exchangers are approximately as follows:
Pressure-temperature charts of individual refrigerants are commonly available on the Internet. For clarity, the pressures bar(g) for refrigerants are summarized in the table
(source A-GAS):
The pressure bar(g) is relative to the
atmospheric pressure (excess pressure to the surrounding air of 1 bar). Some
refrigerants (e.g. R407C) are a mixture of several refrigerants, each having
their own condensing temperatures.
As a result, two temperatures are indicated for these refrigerants:
a) Boiling Temperature refers to the point at which the
liquid refrigerant begins to boil and transitions into a vapour
state.
b) Condensing Temperature represents the point at which the
vapour refrigerant begins to condense back into a liquid
state.
Heat pump freezing, heat exchanger failure
The exchanger rupture most often happens in these two cases:
The operating pressure of the refrigerant is higher than the design pressure of
the exchanger. The system must include a high pressure switch. This switches
off the compressor when the working pressure is exceeded (e.g. in the event
of a fault).
The heat exchanger must not get frozen. There is a risk of freezing the media inside condenser
when the heat pump is running in reverse. Reverse operation is started for a few
minutes to defrost the evaporator. Also, when starting cold, the evaporator
temperature is very low, the evaporator can freeze.
The refrigerant can have a temperature
of -20 °C. Therefore, under unfavorable
circumstances, there is a risk of water freezing in the condenser. Even if the water at the exchanger outlet is 3 °C,
inside the heat exchanger might be a space with a temperature below freezing point. Measures against freezing are, for example:
Temperature sensor at the outlet of the water from the heat exchanger: when it drops below a certain temperature, the compressor turns off.
Antifreeze, electric heating of the exchanger during reverse.
Flow switch: to prevent the exchanger from freezing, it is necessary to maintain full flow on the water side: use the constant speed on the circulation pump. The valves on the radiators must be open.
Strainer at the water inlet of the heat exchanger to capture particles over 1 mm. Dirt can block flow and cause the water in the channel to freeze.
Delayed water pump stop when stopping the compressor. The pump can be allowed to run for some minutes after the compressor is stopped and vice versa: start the water pump before starting the compressor.
Stopping the fan during the defrost cycle raises the evaporator temperature.
The compressor is started at as low a capacity as possible. This will minimize the fall in evaporation temperature during the start-up.
Air conditioning units are optimized for summer operation. When modified into a heat pump, there may be increased difficulties with frost on the outdoor unit equipped with a fan. This is because air conditioning units have smaller gaps between the fins compared to typical heat pumps.
Freezing water in the heat exchanger means damaging the heat exchanger and
usually also the overall damage to the heat pump (water might get into the refrigerant
circuit). That's why SWEP also supplies a special version of the most commonly
used SWEP B26H heat exchanger for R410A refrigerant: the modified
B26FH version
has no channels in the corner at the refrigerant inlet, where the exchanger
is most susceptible to freezing. This reduces the overall risk of the "heat pump
freezing".
Evaporator for heat pump
The evaporator is the heat pump exchanger on its primary circuit. In this
exchanger, the cold liquid refrigerant evaporates. The system is usually set so
that the expansion valve in front of the evaporator reduces the pressure. This
reduces the boiling temperature. The evaporator refrigerant temperature is set
to a temperature of about 0 °C, but it may be less. Heat must be supplied to
the refrigerant in order for the refrigerant to evaporate. This is taken, for
example, from the ambient air or from the ground (and later transferred to the
heating water in the condenser). Most of the energy that is thus transferred
from the environment to the refrigerant is stored in the change of state.
For small applications, the classic SWEP plate heat exchanger can be used.
The refrigerant inlet connection should never be larger than the refrigerant
outlet connection. For proper operation, the recommended refrigerant speed of
10 to 25 m/s at the inlet and 5 to 10 m/s at the outlet (2.5 to 5 m/s if
the connection is horizontal) should be ensured; this also prevents oil
accumulation in the heat exchanger.
High performance pumps require more plates in the exchanger. If more than 30
plates are needed for the evaporator, it is usually necessary to select a
specialized type of plate heat exchanger
(V-type, P-type, F-type or Q-type).
V-series heat exchangers are classic heat exchangers equipped with a system for
even distribution of refrigerant (e.g. V25, V80). Without this measure, with a
larger number of plates, the refrigerant would only flow through the plates
closest to the inlet. The exchanger would not have the expected efficiency
and could get frozen. The distribution system is not an obstacle if such
exchanger is used also as a condenser.
Specialized types (i.e. most of V-series heat exchangers and especially P-type and other evaporators) are not in stock and must be manufactured.
Separation exchanger for heat pump
The separation exchanger is used, for example, to separate the antifreeze
circuit from the heating water circuit. Then a mixture with glycol can be used
outside and there is only heating water in the heating circuit inside the
building. The separation exchanger can also be used to separate the heat pump
from dirty or aggressive media.
To maintain the efficiency of the heat pump, it is necessary to bring the
temperatures of both circuits as close as possible. The pressure losses increase with the square of the flow rate.